Loads and other elements
You place elements from the LOADS panel. Double-click an element on the drawing to open its window and set it up.
Every element has an ID. No two elements in a project can have the same ID.
Pillars and poles
A pillar or pole is where customers connect to the network.
- Config sets the pillar’s fuse ways, for example a number of fuses with a street light fuse or a load fuse.
- Each fuse way takes one Load from the library and a Qty from 1 to 999. A load that uses two or three phases takes two or three fuse ways.
- A Balanced load is a load whose customers VDZ spreads evenly over phases A, B and C.
- Click a load’s data button to see what the library holds for it: demand, standard deviation, power factor, phases and current.
A street light fuse on a pillar protects a light, pit or switchboard that you choose from the list.
A load fuse protects a switchboard that you choose from the list, of either type. VDZ works out its EFLI from the pillar. A switchboard keeps its own loads. Or choose Direct load and type the load in. A direct load counts in the voltage drop on the mains.
To choose what a newly placed pillar or pole starts as, see Preferences.
CFS pillars
A pillar with a combined fuse switch (CFS) feeds larger loads. Each output takes a motor or a direct load that you type in, or a motor or switchboard on the drawing that you link to it. VDZ suggests the CFS fuse from the total current and warns you when the total is over the unit’s frame size.
Street lights
Set the luminaire’s Watts and PF. VDZ works out the current. If you know the running current, type it in and VDZ uses your figure.
Pole Cable is the length of cable from the light’s protection device up the pole to the luminaire. VDZ uses it for the EFLI at the luminaire.
Pits
A plain pit is looped in and out. Tick Fused when the pit has its own protection device. The pit then protects what it feeds, for example a street light.
Switchboards
A switchboard is one of two types.
| Type | Meaning |
|---|---|
| Distribution Board | Its ways protect the elements that are cabled from it. |
| Load | The board is a customer load. You give its maximum demand. |
For a Load, type the AS/NZS 3000 maximum demand on each phase, or a kVA rating. VDZ uses the figure as you enter it. It applies no diversity.
Motors
Type the motor’s nameplate: rating in kW, phases, power factor and efficiency. VDZ works out the rated current from the kW. If you type a rated current, VDZ uses it. Type 0 to have VDZ work it out again.
Under Starting, choose the start method (DOL, star-delta, soft start or VSD), the starts per hour, and the starting current. VDZ shows the voltage dip at the motor and at the pillar or pole that feeds it.
Protection devices
Lights, fused pits and switchboard ways have a protection device. Choose its Rating and Type: a Type B, C or D circuit breaker, or a fuse with a 0.4s or 5s disconnection time. VDZ reads the device’s maximum Zs from the library and checks the EFLI against it.
If the library has no maximum Zs for a device, VDZ lists an issue and does not check what the device protects.