Calculations and results

VDZ calculates as you draw. You do not need to run the main calculation.

Figures appear when both of these are true:

  • the project has its library;
  • every cable has a cable type and a length.

Project settings

The PROJECT panel sets the basis of the calculation.

SettingMeaning
LoadingThe transformer’s loading limit: how far over its rating it may run. When you pick a loading class, VDZ switches Study to the preset that the library gives for that class, if there is one.
StudyThe study preset: the confidence factors, the unbalance factor, the default customer load and the transformer impedance.
FeederThe feeder type. It sets the voltage drop limit.
MethodThe calculation method. It was chosen when the project was created and cannot be changed.

Calculation methods

Multi-Stat is the statistical method of the Joint Supply and Planning Manual (STNW3470). Energex and Ergon Energy assess LV designs with this method.

Monte Carlo simulates thousands of peak-demand moments. In each one, every customer draws a randomly sampled load, and VDZ solves the unbalanced network. Monte Carlo is a supplementary check. It is not a JSPM method. See Monte Carlo.

The transformer totals

The TRANSFORMER panel shows the totals for every fuse circuit together.

FigureMeaning
Source (V), Nominal (V)The voltages from the library.
Z (Source)The source impedance.
I (Total)The total current against the transformer’s rated current.
CustomersThe number of customers on the transformer.
DemandThe demand against the transformer’s kVA rating.
Max DropThe worst voltage drop against the limit.

Figures on the drawing

The ANALYSIS group on the Network tab switches figures on and off.

ButtonShows
Volt dropThe voltage drop under each load.
Worst VDThe voltage drop of the worst phase under each load.
LoadsThe loads under each pillar.
EFLIThe earth fault loop impedance under each load.
WarningsWarnings on cables.

The Overview window

Click Overview to open it. It covers the fuse circuit whose tab is open.

  • SUMMARY shows the circuit, its fuse, demand, current, number of loads and customers, and the worst case.
  • LOAD DATA lists each load with its quantity, the voltage drop on phases A, B and C, and its EFLI.

Export PDF at the foot of the window exports the report.

Issues

The ISSUES panel lists what VDZ found wrong. Click an issue to find the item on the drawing. Copy and Copy All put the lines on the clipboard.

IssueWhat to do
No length, or no cable codeGive the cable a type and a length. Calculations cannot run without them.
Current is over the cable’s ratingUse a larger cable or move load to another circuit.
Fuse is over the cable’s ratingUse a larger cable or a smaller fuse.
Drop is over the limitShorten the run, use a larger cable, or move load.
Zs is over the maximum for the deviceUse a larger cable, move tie points, add a transformer, or fit an intermediate fuse.
An ID is shared by two elementsGive one element another ID.
The project’s library is not in the Library folderSee Libraries.
No max Zs for a deviceThe library has no figure for this device, so what it protects is not checked. Choose another device or ask whoever maintains the library.

Monte Carlo

The Monte Carlo tools are hidden at first. To show them, turn on Show Monte Carlo in Preferences. The Network tab then has a MONTE CARLO group with Run Calc and Advanced study.

Use Monte Carlo to:

  • see the spread of voltages that each customer is likely to get, not only the design case;
  • check phase unbalance and neutral voltage shift;
  • compare options that both pass Multi-Stat, for example a different phase allocation;
  • check a design that is close to the limit.

Click Run Calc to run the simulation. Unlike the Multi-Stat figures, Monte Carlo results do not update by themselves. When you change the drawing, the library or the study settings, run it again.

Results change slightly from run to run. To repeat a run exactly, tick Fixed Seed in Advanced study.

In a Multi-Stat project, compliance is decided by Multi-Stat. Treat the Monte Carlo result as supporting evidence.