Calculations and results
VDZ calculates as you draw. You do not need to run the main calculation.
Figures appear when both of these are true:
- the project has its library;
- every cable has a cable type and a length.
Project settings
The PROJECT panel sets the basis of the calculation.
| Setting | Meaning |
|---|---|
| Loading | The transformer’s loading limit: how far over its rating it may run. When you pick a loading class, VDZ switches Study to the preset that the library gives for that class, if there is one. |
| Study | The study preset: the confidence factors, the unbalance factor, the default customer load and the transformer impedance. |
| Feeder | The feeder type. It sets the voltage drop limit. |
| Method | The calculation method. It was chosen when the project was created and cannot be changed. |
Calculation methods
Multi-Stat is the statistical method of the Joint Supply and Planning Manual (STNW3470). Energex and Ergon Energy assess LV designs with this method.
Monte Carlo simulates thousands of peak-demand moments. In each one, every customer draws a randomly sampled load, and VDZ solves the unbalanced network. Monte Carlo is a supplementary check. It is not a JSPM method. See Monte Carlo.
The transformer totals
The TRANSFORMER panel shows the totals for every fuse circuit together.
| Figure | Meaning |
|---|---|
| Source (V), Nominal (V) | The voltages from the library. |
| Z (Source) | The source impedance. |
| I (Total) | The total current against the transformer’s rated current. |
| Customers | The number of customers on the transformer. |
| Demand | The demand against the transformer’s kVA rating. |
| Max Drop | The worst voltage drop against the limit. |
Figures on the drawing
The ANALYSIS group on the Network tab switches figures on and off.
| Button | Shows |
|---|---|
| Volt drop | The voltage drop under each load. |
| Worst VD | The voltage drop of the worst phase under each load. |
| Loads | The loads under each pillar. |
| EFLI | The earth fault loop impedance under each load. |
| Warnings | Warnings on cables. |
The Overview window
Click Overview to open it. It covers the fuse circuit whose tab is open.
- SUMMARY shows the circuit, its fuse, demand, current, number of loads and customers, and the worst case.
- LOAD DATA lists each load with its quantity, the voltage drop on phases A, B and C, and its EFLI.
Export PDF at the foot of the window exports the report.
Issues
The ISSUES panel lists what VDZ found wrong. Click an issue to find the item on the drawing. Copy and Copy All put the lines on the clipboard.
| Issue | What to do |
|---|---|
| No length, or no cable code | Give the cable a type and a length. Calculations cannot run without them. |
| Current is over the cable’s rating | Use a larger cable or move load to another circuit. |
| Fuse is over the cable’s rating | Use a larger cable or a smaller fuse. |
| Drop is over the limit | Shorten the run, use a larger cable, or move load. |
| Zs is over the maximum for the device | Use a larger cable, move tie points, add a transformer, or fit an intermediate fuse. |
| An ID is shared by two elements | Give one element another ID. |
| The project’s library is not in the Library folder | See Libraries. |
| No max Zs for a device | The library has no figure for this device, so what it protects is not checked. Choose another device or ask whoever maintains the library. |
Monte Carlo
The Monte Carlo tools are hidden at first. To show them, turn on Show Monte Carlo in Preferences. The Network tab then has a MONTE CARLO group with Run Calc and Advanced study.
Use Monte Carlo to:
- see the spread of voltages that each customer is likely to get, not only the design case;
- check phase unbalance and neutral voltage shift;
- compare options that both pass Multi-Stat, for example a different phase allocation;
- check a design that is close to the limit.
Click Run Calc to run the simulation. Unlike the Multi-Stat figures, Monte Carlo results do not update by themselves. When you change the drawing, the library or the study settings, run it again.
Results change slightly from run to run. To repeat a run exactly, tick Fixed Seed in Advanced study.
In a Multi-Stat project, compliance is decided by Multi-Stat. Treat the Monte Carlo result as supporting evidence.